A. General. The fire flow calculation area shall be the total floor area of all floor levels within the exterior walls, and under the horizontal projections of the roof of a building except for Type IA and 1B construction buildings.

B. Area Separations. Portions of buildings which are separated by fire walls without openings, constructed in accordance with the International Building Code, are allowed to be considered as separate fire flow calculation areas.

C. Type 1A and 1B Construction. The fire flow calculation area of buildings constructed of Type 1A and Type 1B construction shall be the area of the three (3) largest successive floors. (Ord. 2801, 3/8/16)